SLA Uptime Calculator

What does 99.9 percent really allow? Enter an availability and see the downtime for every period, or combine components in series and parallel.

Free, no sign-up. Runs in your browser: nothing is uploaded.

How to use SLA Uptime Calculator

  1. Choose what to calculate.
  2. Enter the percentage, downtime or components.
  3. Read the downtime table.

Features

  • Downtime per day, week, month, quarter and year
  • Availability from downtime
  • Series and parallel combinations
  • Table of nines from 90 to 99.9999
  • Readable durations
  • Notes on how SLAs are measured

Supported formats

Input

  • Availability percentage or downtime

You get

  • Allowed downtime per period
  • Matching percentage

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the SLA Uptime Calculator is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • Months are taken as 30 days and years as 365 days.
  • Combining components assumes failures are independent.

Guide

What uptime percentages mean in minutes of downtime

“Three nines” sounds close to perfect until you convert it to minutes. Service level agreements promise a percentage of time, and the number only becomes meaningful when it is translated into the longest outage you would have to accept. The page does that conversion in both directions and adds a model for combining components.

From percentage to time

The share of time a service may be down is 100 minus the availability. For 99.9 percent that is 0.1 percent. A day has 86,400 seconds, so the allowance is 86.4 seconds, which the page shows as 1 min 26.4 s. Scaling up gives 10 min 4.8 s a week, 43 min 12 s in a 30-day month and 8 h 45 min 36 s in a 365-day year. The same method for 99.99 percent gives 4 min 19.2 s per month and 52 min 33.6 s per year, and 99.999 percent leaves about 25.9 seconds and 5 min 15.4 s.

The four modes

“Downtime allowed by an uptime percentage” is the default. “Uptime percentage from downtime” works the other way: enter minutes of outage in a period and see the achieved availability. “Several components that all must work (in series)” multiplies availabilities, so a chain of a load balancer, an application server and a database each at 99.9 percent yields 99.7 percent, noticeably worse than each part. “Redundant components (in parallel)” combines them as 1 − (1 − a)(1 − b); presets include three nines, four nines and two servers in parallel.

Reading the contract, not just the number

The same percentage can mean very different protection. Contracts differ in the measuring period (month or year), in what counts as downtime (complete unavailability or degraded response), in exclusions for planned maintenance, and in the remedy, usually a service credit that is far smaller than the cost of an outage. A higher percentage over a shorter period is stricter: 99.9 percent per month allows 43 minutes at a time, while 99.9 percent per year allows nearly nine hours in total. Check the definitions before comparing offers.

A worked example

At 99.9 % the page lists 1 min 26.4 s per day, 10 min 4.8 s per week, 43 min 12 s per month, 2 h 11 min 24 s per quarter and 8 h 45 min 36 s per year. Choose “two servers in parallel” at 99 percent each, and the combined availability is 99.99 %, which allows only 4 min 19.2 s a month. The series example is the opposite: two components at 99.9 percent give 0.999 × 0.999 = 99.8001 percent.

Limits

The parallel model assumes independent failures. In real systems the two servers may share a power feed, a switch, a software bug or an operator, which brings the true figure well below the calculation. The page uses fixed month and year lengths, so it does not account for leap years or the exact number of days in a month. It converts and combines numbers; it does not measure a service. Uptime of a link also depends on the physical path, which the Fibre Loss Budget Calculator helps check.

Checked against the current version of the SLA Uptime Calculator on .

Frequently asked questions

Is 99.9 percent a lot of downtime?

Over a year it allows almost nine hours, and over a 30-day month about 43 minutes. That is plenty for a single long outage, which is why services that must stay up target more nines or redundancy.

Why do two 99 percent servers in parallel reach 99.99 percent?

The pair is down only when both are down at once. With independent failures that probability is 1 percent times 1 percent, which is 0.01 percent, so availability is 99.99 percent.

How much downtime is 99.9 percent a year?

About 8 hours 45 minutes 36 seconds in a 365-day year, or 43 minutes 12 seconds in a 30-day month.

Does redundancy always raise availability?

Only if failures are independent and failover works. Two servers at 99 percent give 99.99 percent in theory, but a shared network or software bug breaks that.