Server Rack Planner

List the devices you want to rack with their height, power and weight. The planner stacks them from the bottom and shows whether they fit and what the rack will draw.

Free, no sign-up. Runs in your browser: nothing is uploaded.

How to use Server Rack Planner

  1. Enter the rack height.
  2. Add equipment with units, watts, weight and quantity.
  3. Read the layout and the totals.

Features

  • Racks of 1 to 60 units
  • Quantities of each device
  • Total power, heat in BTU/h and current at 120 V and 230 V
  • Total weight
  • Layout table with unit numbers
  • Warnings when full

Supported formats

Input

  • Equipment heights and power

You get

  • Rack layout
  • Space and power totals

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the Server Rack Planner is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • It works from the heights and power you enter; real depth, weight and airflow limits are not checked.
  • Layouts are not saved on any server.

Guide

Planning rack space, power, heat and weight before installation

A rack is a small budget with four lines: space, power, cooling and weight. Running out of any one of them stops a deployment, and they are easy to overlook until the equipment has arrived. The planner takes the list of devices you intend to install and totals all four, with a diagram of which unit each occupies.

What you enter

Set the rack height in units, then add equipment: a name, height in U, power draw in watts, weight in kilograms and a quantity. Quantity expands into numbered copies in the layout, such as “Server (3 of 6)”. The Sample button loads a complete small plan. Equipment is stacked from the bottom in the order of the list, so list heavy items first, and a final line reports the free space above.

The conversions

A rack unit is 44.45 mm (1.75 in), and a standard full-height rack is 42U, though 45U, 48U and half-height cabinets exist. Power ends up as heat, so the heat load in BTU per hour is the watts times 3.412. Current follows from power divided by voltage, so the page shows the amps at both 230 V and 120 V. Electrical codes and good practice keep a circuit below about 80 percent of its rating for continuous loads, so a 16 A circuit should carry no more than about 12.8 A. Use the nameplate or measured power rather than the maximum PSU rating when you have it, since most devices run well below the maximum.

What it does not know

The planner counts height, power and weight but not depth, mounting rails, cable management, airflow direction or blanking panels. Equipment that is deeper than the rack, hot-aisle and cold-aisle layout, power distribution units, and the floor’s load capacity are outside the calculation. Also check the rack’s rated weight capacity and the cooling available at the location, since a rack can fit physically and still overheat the room.

A worked example

The sample plan has two patch panels, two 48-port switches, two firewalls, six servers of 2U, a 4U storage array and a 3U UPS. That is 25 of 42 units (60 %), leaving 17 free. The total draw is 4,130 W, which is 14,092 BTU/h (4,130 × 3.412), or 18.0 A at 230 V and 34.4 A at 120 V. The weight is 263 kg. In the layout the patch panels occupy U1 and U2, the switches U3 and U4, the firewalls U5 and U6, the servers U7 to U18, the storage array U19 to U22 and the UPS U23 to U25. U26 to U42 are free.

Limits

The figures are as good as the numbers you enter. Manufacturers list a maximum draw and a typical draw, and the difference can be large, so choose one deliberately. The page does not store the plan on a server; it stays in your browser. Network cabling for the rack, including the length limits, is in the Network Cable Chart, and the storage you are installing can be sized with the RAID Calculator.

Checked against the current version of the Server Rack Planner on .

Frequently asked questions

Why should heavy equipment go low in the rack?

It lowers the centre of gravity so a loaded rack is less likely to tip, and it keeps the heaviest items within easy reach for lifting. Switches and patch panels, which are light, go higher.

How is cooling capacity related to the BTU figure?

Nearly all the electrical power a device draws ends up as heat, so the BTU per hour figure is the heat the room's cooling must remove. Cooling is often rated in BTU/h or kW; 1 kW is 3,412 BTU/h.

How tall is one rack unit?

44.45 mm (1.75 inches). A 42U rack therefore has 1,867 mm (73.5 inches) of usable mounting height.

How do I convert watts into cooling load?

One watt of power becomes 3.412 BTU per hour of heat, so 2,100 W is about 7,165 BTU/h.