Wire gauge, resistance and voltage drop: choosing the right cable for a run
Every wire has resistance, and current flowing through it loses some voltage along the way, heats the cable and wastes power. On long runs and low-voltage supplies this matters more than anything else about the cable. This calculator gives the properties of a gauge and the voltage drop for a given run, or works backwards from the drop you will accept to the thinnest wire that meets it.
American Wire Gauge
AWG is a logarithmic scale in which each step of three gauges halves the area and each step of six halves the diameter. It is defined from two anchors, 0.127 mm at gauge 36 and 11.684 mm at 0000, 39 steps apart, and the diameter of gauge n is 0.127 mm × 92^((36 − n) / 39). So AWG 10 is 2.588 mm across (5.261 mm²), AWG 12 is 2.053 mm (3.309 mm²) and AWG 24 is about 0.51 mm. Thicker sizes have lower numbers; 00, 000 and 0000 are entered as −1, −2 and −3. If your cable is specified in mm², choose that input instead.
Resistance of a run
The resistance of a conductor is its resistivity times its length divided by its cross-section. The tool uses annealed copper at 1.724 × 10⁻⁸ Ω·m at 20 °C or aluminium at 2.82 × 10⁻⁸ Ω·m, and corrects for temperature with a coefficient of about 0.0039 per °C. Hot wire has more resistance: copper at 70 °C is about 20% higher than at 20 °C. Enter the wire temperature if it will run warm. Length can be in metres or feet, and a two-wire circuit counts the length twice.
Voltage drop and lost power
The drop is current times the resistance of the run, shown in volts and as a share of the supply. The tool also gives the voltage left at the load and the power lost in the wire, I² × R, which becomes heat. For AWG 12 over 10 m each way with 15 A at 12 V, the loop resistance is 104.2 mΩ, so 1.563 V is lost, 13.03% of the supply, and 23.4 W heats the cable. That is a poor design; the table below the results shows the same run in every second gauge from 0 to 30, and AWG 6 would bring it near 3.2%.
Sizing for a drop limit
Choose the second mode, enter the current, supply, length and the largest drop you accept, and the page gives the smallest cross-section that meets it, the AWG that is thick enough and the next standard metric size. For a 230 V circuit of 50 m each way carrying 16 A with a 3% limit, the answer is 3.998 mm², so AWG 11 or the standard 4 mm² cable, which drops 6.9 V.
Solar and low-voltage examples
A 4 mm² solar cable carrying 8 A over 15 m each way at 24 V and 40 °C has a loop resistance of 139.5 mΩ, drops 1.116 V (4.65%) and loses 8.93 W. The temperature term makes a difference here, because roof cables get hot. Doubling the cross-section halves the drop, which is why long panel runs are often 6 mm² or 10 mm².
Limits
This tool computes resistance and voltage drop only. A wire’s safe current depends on its insulation, how it is bundled, the ambient temperature, the length of the run and the rules in force where you live, and sometimes a wire thick enough for the drop is still too thin for the current. It also treats DC; at mains frequency over large cables skin effect and reactance add a little. Consult the applicable code or a qualified electrician for any installed wiring.
Related tools
- AWG to mm Converter lists wire diameters without the circuit calculation.
- Amps to Watts Calculator converts the load current to power.
- Ohm’s Law Calculator covers the voltage, current and resistance relationship behind the drop.
- PCB Trace Width Calculator is the printed-circuit equivalent of choosing a wire size.
Checked against the current version of the Wire Gauge Calculator on .