Wire Gauge Calculator

For automotive, solar, LED and workshop wiring: choose a wire that keeps the voltage drop and the lost power small.

Free, no sign-up. Runs in your browser: nothing is uploaded.

Free workspace included. Docs, spreadsheets, notes and tasks that save on your device. No sign-up.Take a look

How to use Wire Gauge Calculator

  1. Enter your numbers, or press a sample to see an example.
  2. Read the results and the table under them.
  3. Copy the results or download the table as a CSV file.

Features

  • AWG from 0000 to 40 or cross-section in mm²
  • Copper or aluminium at any temperature
  • Voltage drop, volts at the load and power lost
  • Smallest wire for a chosen drop
  • A table of gauges for the same run

Supported formats

Input

  • Typed numbers

You get

  • On-screen results
  • Copyable text
  • CSV table

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the Wire Gauge Calculator is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • It calculates voltage drop and resistance only; the safe current rating of a wire depends on insulation, bundling and local rules and is not given.
  • It is a calculation aid. Electrical, structural and gas work must follow local codes and be checked by a qualified person.

Guide

Wire gauge, resistance and voltage drop: choosing the right cable for a run

Every wire has resistance, and current flowing through it loses some voltage along the way, heats the cable and wastes power. On long runs and low-voltage supplies this matters more than anything else about the cable. This calculator gives the properties of a gauge and the voltage drop for a given run, or works backwards from the drop you will accept to the thinnest wire that meets it.

American Wire Gauge

AWG is a logarithmic scale in which each step of three gauges halves the area and each step of six halves the diameter. It is defined from two anchors, 0.127 mm at gauge 36 and 11.684 mm at 0000, 39 steps apart, and the diameter of gauge n is 0.127 mm × 92^((36 − n) / 39). So AWG 10 is 2.588 mm across (5.261 mm²), AWG 12 is 2.053 mm (3.309 mm²) and AWG 24 is about 0.51 mm. Thicker sizes have lower numbers; 00, 000 and 0000 are entered as −1, −2 and −3. If your cable is specified in mm², choose that input instead.

Resistance of a run

The resistance of a conductor is its resistivity times its length divided by its cross-section. The tool uses annealed copper at 1.724 × 10⁻⁸ Ω·m at 20 °C or aluminium at 2.82 × 10⁻⁸ Ω·m, and corrects for temperature with a coefficient of about 0.0039 per °C. Hot wire has more resistance: copper at 70 °C is about 20% higher than at 20 °C. Enter the wire temperature if it will run warm. Length can be in metres or feet, and a two-wire circuit counts the length twice.

Voltage drop and lost power

The drop is current times the resistance of the run, shown in volts and as a share of the supply. The tool also gives the voltage left at the load and the power lost in the wire, I² × R, which becomes heat. For AWG 12 over 10 m each way with 15 A at 12 V, the loop resistance is 104.2 mΩ, so 1.563 V is lost, 13.03% of the supply, and 23.4 W heats the cable. That is a poor design; the table below the results shows the same run in every second gauge from 0 to 30, and AWG 6 would bring it near 3.2%.

Sizing for a drop limit

Choose the second mode, enter the current, supply, length and the largest drop you accept, and the page gives the smallest cross-section that meets it, the AWG that is thick enough and the next standard metric size. For a 230 V circuit of 50 m each way carrying 16 A with a 3% limit, the answer is 3.998 mm², so AWG 11 or the standard 4 mm² cable, which drops 6.9 V.

Solar and low-voltage examples

A 4 mm² solar cable carrying 8 A over 15 m each way at 24 V and 40 °C has a loop resistance of 139.5 mΩ, drops 1.116 V (4.65%) and loses 8.93 W. The temperature term makes a difference here, because roof cables get hot. Doubling the cross-section halves the drop, which is why long panel runs are often 6 mm² or 10 mm².

Limits

This tool computes resistance and voltage drop only. A wire’s safe current depends on its insulation, how it is bundled, the ambient temperature, the length of the run and the rules in force where you live, and sometimes a wire thick enough for the drop is still too thin for the current. It also treats DC; at mains frequency over large cables skin effect and reactance add a little. Consult the applicable code or a qualified electrician for any installed wiring.

Checked against the current version of the Wire Gauge Calculator on .

Frequently asked questions

Why does a 12 V circuit need such thick wire?

The drop is a fixed number of volts for a given current and wire, so on a low supply it is a much larger share. A drop of 1.5 V is under 1% of 230 V mains but 12.5% of a 12 V battery system, and it also means less voltage at the load. That is why vehicle, boat and solar wiring uses thick cables over any length.

Should I count the return wire?

Yes for a two-wire circuit. Current flows out on one wire and back on the other, so the resistance is that of twice the one-way length. The tool defaults to out and back; switch to one way only if the return path is something else, such as a chassis, with negligible resistance.

What voltage drop is acceptable?

Many installations aim for 3% or less for a branch circuit, and 2% or less for sensitive or low-voltage loads. Check the rules that apply to your work.

Does thicker wire always mean it is safe?

No, voltage drop is only one limit. A wire also has a current rating that depends on its insulation, bundling and surroundings, which this tool does not calculate.