1. Home
  2. Converters
  3. AWG to mm

AWG to mm

For makers and electricians choosing wire between American and metric sizes.

Free, no sign-up. Runs in your browser: nothing is uploaded.

Free workspace included. Docs, spreadsheets, notes and tasks that save on your device. No sign-up.Take a look

How to use AWG to mm

  1. Type a value and check the two units.
  2. Read the result, the formula and the table.
  3. Copy the number, or swap the direction.

Features

  • AWG, diameter, area both ways
  • Copper resistance at 20 °C
  • Chart of AWG 0000 to 40
  • Nearest AWG finder
  • Formula shown

Supported formats

Input

  • A typed number

You get

  • On-screen result
  • AWG chart

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the AWG to mm is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • The tool gives geometry and copper resistance only; current ratings depend on insulation, bundling and temperature.
  • Diameters are the theoretical solid-wire values.

Guide

AWG to mm: wire diameter, cross-section and copper resistance

Electrical wire in North America is sold by American Wire Gauge, while the rest of the world quotes diameter in millimeters or the cross-sectional area in square millimeters. A datasheet in one system has to be read against a cable in another, and the AWG scale, which runs backwards and in odd steps, is the cause of most confusion. This page converts an AWG number to diameter, area and resistance, and works backward from a size in mm or mm².

The AWG formula

AWG is defined by two anchor sizes: 0.005 in for AWG 36 and 0.4600 in for AWG 0000, with 39 geometric steps between them. This gives the diameter in millimeters as d = 0.127 × 92^((36 − n)/39). Each step multiplies the diameter by about 1.1229, so six gauge numbers double the diameter and three numbers halve the area. The numbers 0000, 000 and 00 are entered as −3, −2 and −1.

Using the converter

Under I know the, choose AWG number, Diameter (mm) or Cross-section (mm²), and enter the Value. The page opens on AWG 14 and shows Diameter 1.6277 mm (0.06408 in), Cross-section 2.0809 mm², Nearest AWG 14 and Copper resistance at 20 °C of 8.28 ohms per km. Sample chips load AWG 14, a 2.5 mm² cable and 0.8 mm wire. AWG entries must be whole numbers from −3 to 40.

The reference table

The table lists AWG 0000 (4/0) through 18 with diameter in mm and inches, area and copper resistance per km. AWG 0000 is 11.684 mm and 107.219 mm², AWG 10 is 2.588 mm and 5.261 mm², AWG 14 is 1.628 mm and 2.081 mm², AWG 18 is 1.024 mm and 0.823 mm². The copper resistance for those four is 0.16, 3.28, 8.28 and 20.95 ohms per km. Thick wire has low resistance.

Resistance

The page computes resistance from the area using a resistivity of 1.724 × 10⁻⁸ Ω·m, the value for annealed copper at 20 °C. A 2.5 mm² conductor gives 6.90 ohms per km and 0.8 mm wire gives 34.30. The figure is for the conductor only. Temperature raises resistance by about 0.4% per degree, stranded wire is slightly higher than solid of the same area and other metals such as aluminum have their own resistivity.

Worked examples

AWG 14 is 1.6277 mm, 0.06408 in and 2.0809 mm², with 8.28 Ω/km. A cable of 2.5 mm² has a diameter of 1.7841 mm and sits nearest AWG 13, which is 2.624 mm². A wire of 0.8 mm diameter has 0.5027 mm², 34.30 Ω/km and nearest AWG 20. AWG 17 is 1.038 mm², about half of AWG 14 at 2.081 mm², which confirms the rule of three numbers per halving of the area.

Metric and AWG sizes

Cables in many countries come in sizes of 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10 mm² and so on, which do not match AWG steps. The nearest AWG gives a rough equivalent for a spec sheet, and may be larger or smaller than the area wanted. Do not substitute one for the other in an installation without checking the rating and the rules, since the current a wire may carry depends on more than its size.

Limits

The page gives dimensions and the resistance of solid copper. It does not give current ratings, voltage drop, insulation thickness, strand counts or the overall diameter of a stranded or insulated cable. Ampacity depends on insulation, bundling, ambient temperature and the electrical code, and must be taken from those sources. For wires thicker than AWG 0000 the tool does not apply, because those sizes are given in circular mils.

Checked against the current version of the AWG to mm on .

Frequently asked questions

Why do thicker wires have smaller gauge numbers?

Because the gauge counts the number of drawing steps that were once needed to pull a wire to its size, and a thinner wire needed more of them. So AWG 4 is 5.189 mm and AWG 18 only 1.024 mm. The scale continues past 1 with 0, 00, 000 and 0000, the last of which is 11.684 mm, or 0.4600 in.

Is a 2.5 mm² cable the same as 13 AWG?

Close but not identical. A 2.5 mm² conductor has a diameter of 1.784 mm, and AWG 13 is 1.828 mm, with an area of 2.624 mm², about 5% more. Metric cables are sold by cross-section and the nearest AWG is only a rough match. The page shows the nearest gauge for a diameter or area but does not equate them.

What is AWG 14 in mm?

AWG 14 is 1.628 mm in diameter with a cross-section of 2.08 mm². Each 3 gauge numbers halve the area.

Can I choose a cable from this chart?

The tool gives geometry and resistance only. Current ratings depend on insulation, bundling and temperature, so use your electrical code.

Keep working with the result

openWorkstand also includes a free workspace with documents, spreadsheets, tasks, projects and a calendar that save to a folder on your computer.