AWG to mm: wire diameter, cross-section and copper resistance
Electrical wire in North America is sold by American Wire Gauge, while the rest of the world quotes diameter in millimeters or the cross-sectional area in square millimeters. A datasheet in one system has to be read against a cable in another, and the AWG scale, which runs backwards and in odd steps, is the cause of most confusion. This page converts an AWG number to diameter, area and resistance, and works backward from a size in mm or mm².
The AWG formula
AWG is defined by two anchor sizes: 0.005 in for AWG 36 and 0.4600 in for AWG 0000, with 39 geometric steps between them. This gives the diameter in millimeters as d = 0.127 × 92^((36 − n)/39). Each step multiplies the diameter by about 1.1229, so six gauge numbers double the diameter and three numbers halve the area. The numbers 0000, 000 and 00 are entered as −3, −2 and −1.
Using the converter
Under I know the, choose AWG number, Diameter (mm) or Cross-section (mm²), and enter the Value. The page opens on AWG 14 and shows Diameter 1.6277 mm (0.06408 in), Cross-section 2.0809 mm², Nearest AWG 14 and Copper resistance at 20 °C of 8.28 ohms per km. Sample chips load AWG 14, a 2.5 mm² cable and 0.8 mm wire. AWG entries must be whole numbers from −3 to 40.
The reference table
The table lists AWG 0000 (4/0) through 18 with diameter in mm and inches, area and copper resistance per km. AWG 0000 is 11.684 mm and 107.219 mm², AWG 10 is 2.588 mm and 5.261 mm², AWG 14 is 1.628 mm and 2.081 mm², AWG 18 is 1.024 mm and 0.823 mm². The copper resistance for those four is 0.16, 3.28, 8.28 and 20.95 ohms per km. Thick wire has low resistance.
Resistance
The page computes resistance from the area using a resistivity of 1.724 × 10⁻⁸ Ω·m, the value for annealed copper at 20 °C. A 2.5 mm² conductor gives 6.90 ohms per km and 0.8 mm wire gives 34.30. The figure is for the conductor only. Temperature raises resistance by about 0.4% per degree, stranded wire is slightly higher than solid of the same area and other metals such as aluminum have their own resistivity.
Worked examples
AWG 14 is 1.6277 mm, 0.06408 in and 2.0809 mm², with 8.28 Ω/km. A cable of 2.5 mm² has a diameter of 1.7841 mm and sits nearest AWG 13, which is 2.624 mm². A wire of 0.8 mm diameter has 0.5027 mm², 34.30 Ω/km and nearest AWG 20. AWG 17 is 1.038 mm², about half of AWG 14 at 2.081 mm², which confirms the rule of three numbers per halving of the area.
Metric and AWG sizes
Cables in many countries come in sizes of 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10 mm² and so on, which do not match AWG steps. The nearest AWG gives a rough equivalent for a spec sheet, and may be larger or smaller than the area wanted. Do not substitute one for the other in an installation without checking the rating and the rules, since the current a wire may carry depends on more than its size.
Limits
The page gives dimensions and the resistance of solid copper. It does not give current ratings, voltage drop, insulation thickness, strand counts or the overall diameter of a stranded or insulated cable. Ampacity depends on insulation, bundling, ambient temperature and the electrical code, and must be taken from those sources. For wires thicker than AWG 0000 the tool does not apply, because those sizes are given in circular mils.