Watts to amps: how much current a load draws
Plugs, circuits and generators are limited by current, while appliances are labelled by power. Anyone adding a heater, a welder or a workshop motor to an existing circuit needs to turn watts into amps to see whether it will fit. This page does that for direct current, single-phase AC and three-phase AC, and includes the power factor that makes motor currents higher than a simple division suggests.
The formulas
Current is power divided by voltage, adjusted for the supply. DC: amps = watts ÷ volts. Single-phase AC: amps = watts ÷ (volts × power factor). Three-phase AC: amps = watts ÷ (√3 × line-to-line volts × power factor), with √3 equal to 1.7321. The power factor is 1 for resistive loads such as heaters and typically 0.8 to 0.9 for motors, so a motor draws more current than a heater of the same power.
Using the converter
Choose Supply and set Work out to Amps, then enter the Watts and Volts, and the Power factor for AC. The page opens on single phase, 2,300 W at 230 V and a power factor of 1, and returns 10 A, 2.3 kW and 2.3 kVA. Sample chips load 2,300 W at 230 V, a 3 kW motor on 400 V three phase and a 60 W bulb at 12 V DC.
Voltage matters
For a fixed power, current falls as voltage rises. 1,500 W is 6.522 A at 230 V, 12.5 A at 120 V and 125 A at 12 V. This is why long, thin low-voltage cables drop a lot of voltage, and why high-voltage lines carry power efficiently. On the page, change the Volts field and watch the Amps row to see the effect. Be sure to enter the actual supply voltage of your circuit.
Reading the result rows
Watts and Kilowatts repeat the load, Amps is the current, Volts is the supply and Apparent power in kVA is volts times amps, multiplied by √3 for three phase. When the power factor is below 1, kVA exceeds kW. Utilities and generator makers use kVA because cables and windings heat with current, not with real power. The note under the results states which formula the page used.
Worked examples
2,300 W at 230 V single phase is 10 A. 2,000 W at 120 V is 16.67 A, which triggers the page’s large-current warning. A 3,000 W motor on 400 V three phase at power factor 0.85 draws 5.094 A, with an apparent power of 3.529 kVA. A 60 W bulb on 12 V DC draws 5 A. A 9 kW three-phase load at 400 V and 0.85 draws 15.28 A. Each value comes from the formulas above.
The 16 A warning
If the result is above 16 A for a DC or single-phase circuit at 250 V or less, the page adds a warning that this is a large current for a household socket circuit. It is a prompt to check, not a statement of any code. The right breaker and cable depend on the installation, the length, the cable type and local regulations, and an electrician must decide them.
Limits
The page assumes a steady load at one power factor. It does not include starting current, which can be several times the running current for a motor, or harmonics from electronic loads, voltage drop on long cables or cable heating. Nameplate power may be output rather than input. Watts, volts and the power factor must be positive, with the power factor not above 1.