Watts to Amps

For anyone who needs the current drawn by a device of known power.

Free, no sign-up. Runs in your browser: nothing is uploaded.

Free workspace included. Docs, spreadsheets, notes and tasks that save on your device. No sign-up.Take a look

How to use Watts to Amps

  1. Type a value and check the two units.
  2. Read the result, the formula and the table.
  3. Copy the number, or swap the direction.

Features

  • DC, 1-phase and 3-phase
  • Power factor input
  • Solve for amps, watts or volts
  • kVA shown
  • Large-current warning

Supported formats

Input

  • A typed number

You get

  • On-screen result

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the Watts to Amps is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • It is a calculation, not an electrical design: choose breakers and cables from your local wiring rules.
  • It assumes a steady load and a fixed power factor.

Guide

Watts to amps: how much current a load draws

Plugs, circuits and generators are limited by current, while appliances are labelled by power. Anyone adding a heater, a welder or a workshop motor to an existing circuit needs to turn watts into amps to see whether it will fit. This page does that for direct current, single-phase AC and three-phase AC, and includes the power factor that makes motor currents higher than a simple division suggests.

The formulas

Current is power divided by voltage, adjusted for the supply. DC: amps = watts ÷ volts. Single-phase AC: amps = watts ÷ (volts × power factor). Three-phase AC: amps = watts ÷ (√3 × line-to-line volts × power factor), with √3 equal to 1.7321. The power factor is 1 for resistive loads such as heaters and typically 0.8 to 0.9 for motors, so a motor draws more current than a heater of the same power.

Using the converter

Choose Supply and set Work out to Amps, then enter the Watts and Volts, and the Power factor for AC. The page opens on single phase, 2,300 W at 230 V and a power factor of 1, and returns 10 A, 2.3 kW and 2.3 kVA. Sample chips load 2,300 W at 230 V, a 3 kW motor on 400 V three phase and a 60 W bulb at 12 V DC.

Voltage matters

For a fixed power, current falls as voltage rises. 1,500 W is 6.522 A at 230 V, 12.5 A at 120 V and 125 A at 12 V. This is why long, thin low-voltage cables drop a lot of voltage, and why high-voltage lines carry power efficiently. On the page, change the Volts field and watch the Amps row to see the effect. Be sure to enter the actual supply voltage of your circuit.

Reading the result rows

Watts and Kilowatts repeat the load, Amps is the current, Volts is the supply and Apparent power in kVA is volts times amps, multiplied by √3 for three phase. When the power factor is below 1, kVA exceeds kW. Utilities and generator makers use kVA because cables and windings heat with current, not with real power. The note under the results states which formula the page used.

Worked examples

2,300 W at 230 V single phase is 10 A. 2,000 W at 120 V is 16.67 A, which triggers the page’s large-current warning. A 3,000 W motor on 400 V three phase at power factor 0.85 draws 5.094 A, with an apparent power of 3.529 kVA. A 60 W bulb on 12 V DC draws 5 A. A 9 kW three-phase load at 400 V and 0.85 draws 15.28 A. Each value comes from the formulas above.

The 16 A warning

If the result is above 16 A for a DC or single-phase circuit at 250 V or less, the page adds a warning that this is a large current for a household socket circuit. It is a prompt to check, not a statement of any code. The right breaker and cable depend on the installation, the length, the cable type and local regulations, and an electrician must decide them.

Limits

The page assumes a steady load at one power factor. It does not include starting current, which can be several times the running current for a motor, or harmonics from electronic loads, voltage drop on long cables or cable heating. Nameplate power may be output rather than input. Watts, volts and the power factor must be positive, with the power factor not above 1.

Checked against the current version of the Watts to Amps on .

Frequently asked questions

Why does a 1,500 W heater draw more amps in the US than in Europe?

Because current is power divided by voltage, so a lower supply voltage means more current for the same watts. A 1,500 W resistive heater draws 6.52 A at 230 V and 12.5 A at 120 V. The page shows both if you change the Volts field, which is why the same appliance needs a heavier cord and circuit in a 120 V country.

How do I find the current of a motor from its kW rating?

Choose three phase, enter the line voltage and the power factor from the nameplate, and type the power in watts. A 3 kW motor on 400 V at 0.85 draws 5.09 A on the page. Nameplate power is usually output at the shaft, so the electrical input is higher by the efficiency, and the real current is a little more than shown.

How many amps is 2,300 watts at 230 V?

Divide watts by volts: 2,300 ÷ 230 = 10 amps for a resistive load at power factor 1.

Can I choose a breaker from this result?

No. A breaker and cable depend on local code, cable length, bundling and the load type. Use the result as a starting estimate and ask an electrician.