Guide
Amps to watts for DC, single-phase and three-phase circuits
An appliance label may give amps and volts but not watts, a plug or a generator may give watts but not amps, and an electrician needs to move between them. The conversion is simple for a battery and slightly more complex for a mains circuit, where the power factor and the number of phases matter. This page calculates watts from amps and volts, and can also solve for the other quantities.
The formulas
For direct current, power in watts is volts times amps. For single-phase alternating current it is volts × amps × power factor. For three-phase it is √3 × line-to-line volts × amps × power factor, where √3 is 1.7321. The power factor ranges from 0 to 1 and is 1 for a purely resistive load. These are the standard relations, and the page shows which one it used in a note under the results.
Using the converter
Choose the Supply, DC, AC single phase or AC three phase, and Work out, Watts, Amps or Volts. Fields for the two known quantities appear, and Power factor appears for AC. The page opens on single phase 10 A at 230 V with a power factor of 1 and gives 2,300 W, 2.3 kW, 10 A, 230 V and 2.3 kVA of apparent power. Sample chips load three cases.
Reading the result rows
Watts is the real power, Kilowatts is the same divided by 1,000, and Amps and Volts repeat the circuit. Apparent power in kVA is volts times amps, or √3 times that for three phase, divided by 1,000. The kVA figure is larger than the kW figure when the power factor is below 1. A generator or transformer is rated in kVA because the current, not the real power, sets its heating.
Worked examples
Single phase, 10 A at 230 V, power factor 1 is 2,300 W. The same current at power factor 0.9 is 2,070 W. A three-phase load of 16 A at 400 V and power factor 0.85 is 9,422.36 W, 9.4224 kW and 11.085 kVA. A 12 V DC circuit with 5 A is 60 W. Solving the other way, 2,300 W at 230 V is 10 A, as the watts-to-amps page confirms.
Which voltage to enter
For three-phase work, enter the voltage between any two lines, which is commonly 400 or 415 V in many countries and 208 or 480 V in others. For single-phase, enter the supply voltage, for instance 230 V or 120 V. If you only know the phase-to-neutral voltage of a three-phase system, multiply it by 1.732 first. The page does not guess which kind you mean, so state it in the Supply field.
Large currents
When the current exceeds 16 A on a DC or single-phase circuit at 250 V or less, the page adds a warning that this is a large current for a household socket circuit. The threshold is a reminder, not a rule, and it does not apply to three-phase supplies. Choose breakers and cables from the local electrical code and a qualified electrician, not from this result.
Limits
The page is an arithmetic tool and not an electrical design. It assumes steady, sinusoidal AC at a single power factor, and it does not model starting currents, harmonics, voltage drop or cable heating. Power factor must be above 0 and not more than 1, and amps, volts and watts must be positive. For household wiring, motors and generators, follow the code and the manufacturer.
Related tools
- Watts to Amps solves for current from a power rating.
- kVA to kW converts the apparent power of generators.
- Wh to mAh handles battery capacity rather than circuits.
- Watts to Horsepower converts motor power into horsepower.
Checked against the current version of the Amps to Watts on .