kVA to kW for generators, transformers and UPS systems
A generator is sold as 100 kVA and a customer asks how many kilowatts that will run. The two units sound alike and are not the same. Kilovolt-amperes measure the apparent power, the product of voltage and current, while kilowatts measure the real power that does work. The gap between them is the power factor, and this page converts in both directions and shows the current the equipment would carry at full load.
The three kinds of power
Apparent power S, in kVA, is voltage times current. Real power P, in kW, is S times the power factor. Reactive power Q, in kVAr, is the part that swaps back and forth with inductors and capacitors and does no work, and S² = P² + Q². A power factor of 1 means all the current is useful, and motors, transformers and fluorescent ballasts lower it. The page shows all three for the values you give.
The conversion
kW = kVA × power factor, and kVA = kW ÷ power factor. At a power factor of 0.8, 100 kVA is 80 kW, and 80 kW is 100 kVA. At 0.9, 100 kVA is 90 kW and the reactive power is 43.6 kVAr. The reactive figure on the page is √(kVA² − kW²). The power factor must be above 0 and at most 1.
Using the converter
Choose Convert, kVA to kW or kW to kVA, enter the Value, Power factor, Supply (three phase or single phase) and Line voltage. The page opens on 100 kVA, power factor 0.8, three phase at 415 V and shows 100 kVA, 80 kW, 60 kVAr and a full load current of 139.12 A. Sample chips load 100 kVA at 0.8 and a 40 kW load to kVA.
Full load current
The current row tells you what the equipment carries at its rating. For three phase, I = kVA × 1,000 ÷ (√3 × V), with V the line-to-line voltage, so 100 kVA at 415 V is 139.12 A. For single phase, I = kVA × 1,000 ÷ V. A 10 kVA single-phase supply at 230 V carries 43.48 A. The page uses the line voltage you enter, so set it to match the supply.
Worked examples
100 kVA at 0.8 is 80 kW and 60 kVAr, with 139.12 A at 415 V three phase. A 40 kW load at 0.8 needs 50 kVA, has 30 kVAr and draws 69.56 A. A 100 kVA set at 0.9 delivers 90 kW. A 10 kVA single-phase unit at 230 V has a full load current of 43.48 A. Each follows from the formulas shown above and agrees with the page.
Sizing and margin
When choosing a generator for a known load, convert the load’s kW to kVA at its power factor, then leave a margin for starting currents, since motors can draw several times their running current for a moment. Equipment makers publish derating for altitude and temperature too. The page does the conversion and does not size the set, which is a decision for an engineer or supplier.
Limits
The page assumes a balanced three-phase load, a steady sinusoidal supply and a single power factor. It does not handle unbalanced phases, harmonic loads, leading power factors or starting surges. The full load current is the rated value, not the actual current in use. For installation design, follow the code and the maker’s documents.