kVA to kW

For people sizing generators, UPS units and transformers.

Free, no sign-up. Runs in your browser: nothing is uploaded.

Free workspace included. Docs, spreadsheets, notes and tasks that save on your device. No sign-up.Take a look

How to use kVA to kW

  1. Type a value and check the two units.
  2. Read the result, the formula and the table.
  3. Copy the number, or swap the direction.

Features

  • kVA and kW both ways
  • Power factor input
  • Reactive power in kVAr
  • Full load current
  • Single and three phase

Supported formats

Input

  • A typed number

You get

  • On-screen result

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the kVA to kW is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • It is a calculation, not an electrical design: choose breakers and cables from your local wiring rules.
  • Generator output also depends on altitude, temperature and the type of load.

Guide

kVA to kW for generators, transformers and UPS systems

A generator is sold as 100 kVA and a customer asks how many kilowatts that will run. The two units sound alike and are not the same. Kilovolt-amperes measure the apparent power, the product of voltage and current, while kilowatts measure the real power that does work. The gap between them is the power factor, and this page converts in both directions and shows the current the equipment would carry at full load.

The three kinds of power

Apparent power S, in kVA, is voltage times current. Real power P, in kW, is S times the power factor. Reactive power Q, in kVAr, is the part that swaps back and forth with inductors and capacitors and does no work, and S² = P² + Q². A power factor of 1 means all the current is useful, and motors, transformers and fluorescent ballasts lower it. The page shows all three for the values you give.

The conversion

kW = kVA × power factor, and kVA = kW ÷ power factor. At a power factor of 0.8, 100 kVA is 80 kW, and 80 kW is 100 kVA. At 0.9, 100 kVA is 90 kW and the reactive power is 43.6 kVAr. The reactive figure on the page is √(kVA² − kW²). The power factor must be above 0 and at most 1.

Using the converter

Choose Convert, kVA to kW or kW to kVA, enter the Value, Power factor, Supply (three phase or single phase) and Line voltage. The page opens on 100 kVA, power factor 0.8, three phase at 415 V and shows 100 kVA, 80 kW, 60 kVAr and a full load current of 139.12 A. Sample chips load 100 kVA at 0.8 and a 40 kW load to kVA.

Full load current

The current row tells you what the equipment carries at its rating. For three phase, I = kVA × 1,000 ÷ (√3 × V), with V the line-to-line voltage, so 100 kVA at 415 V is 139.12 A. For single phase, I = kVA × 1,000 ÷ V. A 10 kVA single-phase supply at 230 V carries 43.48 A. The page uses the line voltage you enter, so set it to match the supply.

Worked examples

100 kVA at 0.8 is 80 kW and 60 kVAr, with 139.12 A at 415 V three phase. A 40 kW load at 0.8 needs 50 kVA, has 30 kVAr and draws 69.56 A. A 100 kVA set at 0.9 delivers 90 kW. A 10 kVA single-phase unit at 230 V has a full load current of 43.48 A. Each follows from the formulas shown above and agrees with the page.

Sizing and margin

When choosing a generator for a known load, convert the load’s kW to kVA at its power factor, then leave a margin for starting currents, since motors can draw several times their running current for a moment. Equipment makers publish derating for altitude and temperature too. The page does the conversion and does not size the set, which is a decision for an engineer or supplier.

Limits

The page assumes a balanced three-phase load, a steady sinusoidal supply and a single power factor. It does not handle unbalanced phases, harmonic loads, leading power factors or starting surges. The full load current is the rated value, not the actual current in use. For installation design, follow the code and the maker’s documents.

  • Amps to Watts calculates real power from a measured current.
  • Watts to Amps works backward from a power to a current.
  • kW to HP converts the kilowatts to horsepower.
  • Hz to RPM relates supply frequency to motor speed.

Checked against the current version of the kVA to kW on .

Frequently asked questions

Why do generators and transformers carry a kVA rating and not a kW one?

Because their windings and cables heat with current, and current depends on the apparent power whatever the load does with it. A load with a poor power factor draws more current for the same real power. A 100 kVA set can therefore supply 80 kW at 0.8, or 90 kW at 0.9, and the kVA figure is the limit that stays fixed.

What power factor should I assume if I do not know it?

The page starts at 0.8, a common default rating for generator sets, and that is a sensible starting point for mixed motor loads. If the load is mainly heaters and lighting, the power factor is close to 1, and a kW load then needs about the same kVA. Check the nameplates of the loads for a real figure.

How do I convert kVA to kW?

Multiply kVA by the power factor: kW = kVA × PF. A 100 kVA generator at 0.8 gives 80 kW.

Why are generators rated in kVA?

Because heating in the windings depends on current, not on the power factor of the load, so the kVA rating describes what the machine can carry.