Guide
Three-phase power: kW, kVA, kVAR, line current and power factor correction
Three-phase supplies deliver most industrial and commercial power, and the formulas for them differ from single-phase ones by a factor of the square root of three. Add a power factor, and sizing a cable, breaker or generator for a motor requires some care. This calculator converts between current and power for either supply, gives the reactive power and, if you ask, the capacitor needed to improve the power factor.
The core formula
In a balanced three-phase system the apparent power in kilovolt-amperes is √3 × the line-to-line voltage × the line current ÷ 1,000. Here √3 is about 1.732. The real power in kilowatts is the apparent power multiplied by the power factor, and the reactive power is the quantity left over: kVAR = √(kVA² − kW²). For a single-phase supply the same formulas apply without the √3.
Using the tool
Choose three-phase or single-phase, then whether to find the power from a current or the current from a power. Enter the line-to-line voltage, the current or the real power and the power factor. For 25 A at 400 V with a power factor of 0.85, the apparent power is 17.321 kVA, the real power 14.722 kW and the reactive power 9.1241 kVAR. For a three-phase load the page also shows the phase voltage of a star connection, 230.94 V here, and the phase current of a delta connection, 14.434 A.
From power to current
For the other direction enter the real power. A 15 kW motor load at 415 V with a power factor of 0.8 has an apparent power of 18.75 kVA and a line current of 26.085 A; the reactive power is 11.25 kVAR. Remember that the nameplate of a motor gives the shaft output, and the electrical input is higher by the inefficiency of the motor, so divide the shaft power by the efficiency first.
Power factor correction
Many loads, especially induction motors, have a lagging power factor because they need reactive power. Capacitors supply it locally. To raise the factor from 0.85 to 0.95 for a 14.722 kW load, the capacitor bank must provide P × (tan φ₁ − tan φ₂) = 4.285 kVAR, where φ is the angle whose cosine is the power factor. After correction the apparent power falls to 15.497 kVA and the line current to 22.368 A. For the 15 kW motor at 0.8, reaching 0.95 needs 6.32 kVAR, and the current falls to 21.966 A. Enter the target power factor, or clear the box to skip it.
Choosing the capacitor
Capacitor banks are sold in steps, so pick the nearest standard size, and avoid over-correcting: too much capacitance makes the power factor leading, which can raise voltage and, with some drives, cause resonance. Systems with many electronic loads can have harmonic currents that overload capacitors, so they may need detuning reactors. A qualified engineer should specify and install a bank.
Limits
The calculation assumes the three phases are balanced and the power factor is steady. A load that varies, unbalanced currents, harmonics from variable-speed drives and the starting current of a motor are not modelled. All wiring, protection and capacitor work must follow local electrical rules and be done by a qualified electrician.
Related tools
- Amps to Watts Calculator converts current and voltage to power on a single-phase supply.
- Watts to Amps Calculator goes the other way for a known load.
- Electricity Cost Calculator turns the load’s energy into money.
- Wire Gauge Calculator checks the voltage drop of the cable that feeds it.
Checked against the current version of the Three-Phase Power Calculator on .