Three-Phase Power Calculator

For electricians, students and plant engineers: size a three-phase load and see how much a capacitor bank improves the power factor.

Free, no sign-up. Runs in your browser: nothing is uploaded.

Free workspace included. Docs, spreadsheets, notes and tasks that save on your device. No sign-up.Take a look

How to use Three-Phase Power Calculator

  1. Enter your numbers, or press a sample to see an example.
  2. Read the results and the table under them.
  3. Copy the results or download the table as a CSV file.

Features

  • kW, kVA, kVAR and line current
  • Three-phase or single-phase
  • Star phase voltage and delta phase current
  • Capacitor kVAR for a target power factor
  • Current after correction

Supported formats

Input

  • Typed numbers

You get

  • On-screen results
  • Copyable text

Private by design

Everything you enter is processed by your browser on this device. Nothing is sent to openWorkstand or anyone else, so the Three-Phase Power Calculator is safe for private and work data. After you have used it once while online, it also works without an internet connection. How local processing works

Good to know

  • It assumes a balanced load and a steady power factor.
  • It is a calculation aid. Electrical, structural and gas work must follow local codes and be checked by a qualified person.

Guide

Three-phase power: kW, kVA, kVAR, line current and power factor correction

Three-phase supplies deliver most industrial and commercial power, and the formulas for them differ from single-phase ones by a factor of the square root of three. Add a power factor, and sizing a cable, breaker or generator for a motor requires some care. This calculator converts between current and power for either supply, gives the reactive power and, if you ask, the capacitor needed to improve the power factor.

The core formula

In a balanced three-phase system the apparent power in kilovolt-amperes is √3 × the line-to-line voltage × the line current ÷ 1,000. Here √3 is about 1.732. The real power in kilowatts is the apparent power multiplied by the power factor, and the reactive power is the quantity left over: kVAR = √(kVA² − kW²). For a single-phase supply the same formulas apply without the √3.

Using the tool

Choose three-phase or single-phase, then whether to find the power from a current or the current from a power. Enter the line-to-line voltage, the current or the real power and the power factor. For 25 A at 400 V with a power factor of 0.85, the apparent power is 17.321 kVA, the real power 14.722 kW and the reactive power 9.1241 kVAR. For a three-phase load the page also shows the phase voltage of a star connection, 230.94 V here, and the phase current of a delta connection, 14.434 A.

From power to current

For the other direction enter the real power. A 15 kW motor load at 415 V with a power factor of 0.8 has an apparent power of 18.75 kVA and a line current of 26.085 A; the reactive power is 11.25 kVAR. Remember that the nameplate of a motor gives the shaft output, and the electrical input is higher by the inefficiency of the motor, so divide the shaft power by the efficiency first.

Power factor correction

Many loads, especially induction motors, have a lagging power factor because they need reactive power. Capacitors supply it locally. To raise the factor from 0.85 to 0.95 for a 14.722 kW load, the capacitor bank must provide P × (tan φ₁ − tan φ₂) = 4.285 kVAR, where φ is the angle whose cosine is the power factor. After correction the apparent power falls to 15.497 kVA and the line current to 22.368 A. For the 15 kW motor at 0.8, reaching 0.95 needs 6.32 kVAR, and the current falls to 21.966 A. Enter the target power factor, or clear the box to skip it.

Choosing the capacitor

Capacitor banks are sold in steps, so pick the nearest standard size, and avoid over-correcting: too much capacitance makes the power factor leading, which can raise voltage and, with some drives, cause resonance. Systems with many electronic loads can have harmonic currents that overload capacitors, so they may need detuning reactors. A qualified engineer should specify and install a bank.

Limits

The calculation assumes the three phases are balanced and the power factor is steady. A load that varies, unbalanced currents, harmonics from variable-speed drives and the starting current of a motor are not modelled. All wiring, protection and capacitor work must follow local electrical rules and be done by a qualified electrician.

Checked against the current version of the Three-Phase Power Calculator on .

Frequently asked questions

Why does a low power factor matter if the kilowatts are the same?

For the same real power, a lower power factor means more current in the cables, transformers and switchgear, which heat up and drop more voltage, and many utilities charge extra for it. At 0.85 the 14.722 kW load draws 25 A; at 0.95 it draws 22.368 A, about 10.5% less. The energy used is the same, but the supply has to be sized for the larger current.

What is the difference between kW and kVA?

Kilowatts are the useful power that turns into work or heat, while kilovolt-amperes are the product of voltage and current that the supply must carry. They are equal only when the power factor is 1. Motors and transformers magnetise their cores, so they draw reactive power, kVAR, that does no work but fills up the cable, and kVA = √(kW² + kVAR²).

What is the formula for three-phase power?

Real power P = √3 × line voltage × line current × power factor, where √3 is about 1.732.

Is the capacitor size exact?

It is the exact value for a steady, balanced load. Real banks come in steps, and varying loads or harmonics need a professional design.